uk = Uk/UN; Ik = IN/uk = IN·UN/Uk
The smaller short-circuit voltage is relative to rated voltage, the greater the unconstrained short-circuit current.
The smaller short-circuit voltage is relative to rated voltage, the greater the unconstrained short-circuit current.
Select a target and calculate.
The smaller short-circuit voltage is relative to rated voltage, the greater the unconstrained short-circuit current.
UN=230 V, Uk=18.3 V and IN=4 A give uk≈7.96% and Ik≈50.3 A.
Rated voltage from an ideal stiff source and a linear transformer equivalent circuit; supply impedance, cables, protection clearing and transient peak current are excluded.
This calculator uses short-circuit voltage as a compact measure of transformer impedance and estimates steady fault current at rated applied voltage.
Uk is the small test voltage that drives IN with the secondary shorted. The ratio uk=Uk/UN scales prospective steady current: Ik=IN/uk.
uk = Uk/UN; Ik = IN/uk = IN·UN/Uk
uk = Uk/UNIk = IN/ukIk = IN·UN/Uk| Symbol / input | Meaning |
|---|---|
| Steady short-circuit current Ik | Symmetrical steady value from the simplified equivalent circuit at rated voltage. |
| Rated voltage UN | Rated voltage on the same transformer side to which rated and short-circuit current refer. |
| Short-circuit voltage Uk | Reduced voltage required in the short-circuit test to make exactly rated current flow. |
| Rated current IN | Rated current on the same winding side as UN and Uk. |
UN, Uk and IN must refer to the same winding side and tap. Uk is a voltage from the short-circuit test; if nameplate uk is given in percent, Uk=uk·UN/100.
Take rated voltage/current from the nameplate and matching short-circuit voltage from test or manufacturer data. Use the result only as transformer contribution and add supply/cable impedances for protection studies.
With 230 V rated voltage, 18.3 V short-circuit voltage and 4 A rated current, uk=7.96% and steady short-circuit current is about 50.3 A.
Lower uk means a stiffer source but greater fault current. This result is neither inrush current nor the first asymmetrical peak.
UN and Uk may use different selectable voltage units because their ratio is formed in SI. IN and Ik refer to the same side.
Preliminary protection estimates, laboratory tests and comparison of transformer impedances.
Simplified steady transformer value; upstream supply, cables, arc impedance, saturation, DC offset and clearing time are excluded.
Common mistake: Do not confuse Uk with UN or mix winding sides. Do not treat the steady value as peak short-circuit current.
Preliminary protection estimates, laboratory tests and comparison of transformer impedances.
UN, Uk and IN must refer to the same winding side and tap. Uk is a voltage from the short-circuit test; if nameplate uk is given in percent, Uk=uk·UN/100.
Simplified steady transformer value; upstream supply, cables, arc impedance, saturation, DC offset and clearing time are excluded.