Transformer short-circuit current

The smaller short-circuit voltage is relative to rated voltage, the greater the unconstrained short-circuit current.

MINTSI
01

Inputs

Symmetrical steady value from the simplified equivalent circuit at rated voltage.

Rated voltage on the same transformer side to which rated and short-circuit current refer.

Reduced voltage required in the short-circuit test to make exactly rated current flow.

Rated current on the same winding side as UN and Uk.

02

Result

Select a target and calculate.

Calculation

uk = Uk/UN; Ik = IN/uk = IN·UN/Uk

The smaller short-circuit voltage is relative to rated voltage, the greater the unconstrained short-circuit current.

Understand the inputs
  • Steady short-circuit current IkSymmetrical steady value from the simplified equivalent circuit at rated voltage.
  • Rated voltage UNRated voltage on the same transformer side to which rated and short-circuit current refer.
  • Short-circuit voltage UkReduced voltage required in the short-circuit test to make exactly rated current flow.
  • Rated current INRated current on the same winding side as UN and Uk.
Example

UN=230 V, Uk=18.3 V and IN=4 A give uk≈7.96% and Ik≈50.3 A.

Assumptions and limits

Rated voltage from an ideal stiff source and a linear transformer equivalent circuit; supply impedance, cables, protection clearing and transient peak current are excluded.

Technical article

Understand Transformer short-circuit current

This calculator uses short-circuit voltage as a compact measure of transformer impedance and estimates steady fault current at rated applied voltage.

What does this quantity describe?

Uk is the small test voltage that drives IN with the secondary shorted. The ratio uk=Uk/UN scales prospective steady current: Ik=IN/uk.

Formula and variables

uk = Uk/UN; Ik = IN/uk = IN·UN/Uk

  • uk = Uk/UN
  • Ik = IN/uk
  • Ik = IN·UN/Uk
Symbol / inputMeaning
Steady short-circuit current IkSymmetrical steady value from the simplified equivalent circuit at rated voltage.
Rated voltage UNRated voltage on the same transformer side to which rated and short-circuit current refer.
Short-circuit voltage UkReduced voltage required in the short-circuit test to make exactly rated current flow.
Rated current INRated current on the same winding side as UN and Uk.

Choose the inputs correctly

UN, Uk and IN must refer to the same winding side and tap. Uk is a voltage from the short-circuit test; if nameplate uk is given in percent, Uk=uk·UN/100.

How to use the calculator

Take rated voltage/current from the nameplate and matching short-circuit voltage from test or manufacturer data. Use the result only as transformer contribution and add supply/cable impedances for protection studies.

Worked example

With 230 V rated voltage, 18.3 V short-circuit voltage and 4 A rated current, uk=7.96% and steady short-circuit current is about 50.3 A.

Understand the result and units

Lower uk means a stiffer source but greater fault current. This result is neither inrush current nor the first asymmetrical peak.

UN and Uk may use different selectable voltage units because their ratio is formed in SI. IN and Ik refer to the same side.

Useful next calculation

Use transformer turns ratio for ideal voltages and wire resistance and voltage drop for a first resistive cable contribution.

Typical applications

Preliminary protection estimates, laboratory tests and comparison of transformer impedances.

Assumptions, limits and common mistakes

Simplified steady transformer value; upstream supply, cables, arc impedance, saturation, DC offset and clearing time are excluded.

Common mistake: Do not confuse Uk with UN or mix winding sides. Do not treat the steady value as peak short-circuit current.

Frequently asked questions

What is “Transformer short-circuit current” used for?

Preliminary protection estimates, laboratory tests and comparison of transformer impedances.

Where do the input values come from?

UN, Uk and IN must refer to the same winding side and tap. Uk is a voltage from the short-circuit test; if nameplate uk is given in percent, Uk=uk·UN/100.

What does the result not cover?

Simplified steady transformer value; upstream supply, cables, arc impedance, saturation, DC offset and clearing time are excluded.

Sources, method and review

  • Rudolf Busch, Elektrotechnik und Elektronik für Maschinenbauer und Verfahrenstechniker, 4th ed. 2006, Abschnitt 8.3.3.2, Kurzschlussversuch (local chapter PDF)

Our method, source hierarchy and automated checks are documented on the methodology page. Read the methodology

Responsible
NormCalc-Redaktion
Last updated