Busch 2006, Abschnitt 8.3.3.3 Betriebsverhalten

Transformer partial-load efficiency

Core loss remains approximately constant while copper loss grows with the square of load fraction.

MINTSI
01

Inputs

Ratio of output real power to useful power plus modelled losses.

Nameplate apparent-power rating; enter its numerical kVA value through this power field.

Current or apparent load divided by rated value; 0.75 means 75% load.

Displacement factor of the connected load at the operating point.

Real power measured at rated voltage in the no-load test, approximately core loss.

Real power measured in the short-circuit test at rated current; scale by β squared at partial load.

02

Result

Select a target and calculate.

Calculation

η = β·SN·cosφ / [β·SN·cosφ + P0 + β²·PkN]

Core loss remains approximately constant while copper loss grows with the square of load fraction.

Understand the inputs
  • Efficiency η (0 to 1)Ratio of output real power to useful power plus modelled losses.
  • Rated apparent power SN in kVANameplate apparent-power rating; enter its numerical kVA value through this power field.
  • Load fraction βCurrent or apparent load divided by rated value; 0.75 means 75% load.
  • Power factor cos φDisplacement factor of the connected load at the operating point.
  • No-load loss P0Real power measured at rated voltage in the no-load test, approximately core loss.
  • Rated copper loss PkNReal power measured in the short-circuit test at rated current; scale by β squared at partial load.
Example

10 kVA, β=0.75, power factor 0.8, P0=120 W and PkN=300 W give P2=6.0 kW and η≈0.954 or 95.4%.

Assumptions and limits

Constant rated voltage, load-independent P0 and constant winding resistance; stray loss, temperature change and harmonics are excluded.

Technical article

Understand Transformer partial-load efficiency

This calculator connects no-load and short-circuit tests to an actual operating point, showing why a lightly loaded transformer may be inefficient despite small absolute loss.

What does this quantity describe?

At constant rated voltage, P0 is treated as nearly constant core loss. Rated-current copper loss PkN falls to β²·PkN at load fraction β. Useful output is β·SN·power factor.

Formula and variables

η = β·SN·cosφ / [β·SN·cosφ + P0 + β²·PkN]

  • P2 = β·SN·cosφ
  • Pcu = β²·PkN
  • η = P2/(P2+P0+Pcu)
Symbol / inputMeaning
Efficiency η (0 to 1)Ratio of output real power to useful power plus modelled losses.
Rated apparent power SN in kVANameplate apparent-power rating; enter its numerical kVA value through this power field.
Load fraction βCurrent or apparent load divided by rated value; 0.75 means 75% load.
Power factor cos φDisplacement factor of the connected load at the operating point.
No-load loss P0Real power measured at rated voltage in the no-load test, approximately core loss.
Rated copper loss PkNReal power measured in the short-circuit test at rated current; scale by β squared at partial load.

Choose the inputs correctly

SN comes from the nameplate. β is actual current or apparent load divided by rated value. Power factor belongs to the load. P0 comes from the no-load test and PkN from the rated-current short-circuit test.

How to use the calculator

Ensure all data refer to the same transformer, tap and temperature condition. Obtain β and power factor at the actual operating point, then compare several load points rather than rated load only.

Worked example

10 kVA at β=0.75 and power factor 0.8 delivers 6.0 kW. With 120 W core loss and 0.75²·300 W=168.75 W copper loss, η=6000/6288.75≈95.4%.

Understand the result and units

At low load P0 dominates; at high load copper loss grows quadratically. Maximum efficiency occurs approximately when the two loss components are equal.

Enter SN numerically in kVA; in the real-power balance 1 kVA contributes 1 kW per unit power factor. P0 and PkN may be entered in watts.

Useful next calculation

Use transformer short-circuit current for fault current and transformer turns ratio for ideal voltages.

Typical applications

Loading comparisons, choosing several small versus one large transformer, and evaluating teaching experiments.

Assumptions, limits and common mistakes

Constant voltage and equivalent losses. Temperature-dependent winding resistance, stray/harmonic loss and thermal transients are excluded.

Common mistake: Do not use apparent power directly as useful real power; power factor is essential. Scale PkN with β squared, not linearly.

Frequently asked questions

What is “Transformer partial-load efficiency” used for?

Loading comparisons, choosing several small versus one large transformer, and evaluating teaching experiments.

Where do the input values come from?

SN comes from the nameplate. β is actual current or apparent load divided by rated value. Power factor belongs to the load. P0 comes from the no-load test and PkN from the rated-current short-circuit test.

What does the result not cover?

Constant voltage and equivalent losses. Temperature-dependent winding resistance, stray/harmonic loss and thermal transients are excluded.

Sources, method and review

  • Rudolf Busch, Elektrotechnik und Elektronik für Maschinenbauer und Verfahrenstechniker, 4th ed. 2006, Abschnitt 8.3.3.3, Betriebsverhalten und Wirkungsgrad (local chapter PDF)

Our method, source hierarchy and automated checks are documented on the methodology page. Read the methodology

Responsible
NormCalc-Redaktion
Last updated
2026-09-16