η = β·SN·cosφ / [β·SN·cosφ + P0 + β²·PkN]
Core loss remains approximately constant while copper loss grows with the square of load fraction.
Core loss remains approximately constant while copper loss grows with the square of load fraction.
Select a target and calculate.
Core loss remains approximately constant while copper loss grows with the square of load fraction.
10 kVA, β=0.75, power factor 0.8, P0=120 W and PkN=300 W give P2=6.0 kW and η≈0.954 or 95.4%.
Constant rated voltage, load-independent P0 and constant winding resistance; stray loss, temperature change and harmonics are excluded.
This calculator connects no-load and short-circuit tests to an actual operating point, showing why a lightly loaded transformer may be inefficient despite small absolute loss.
At constant rated voltage, P0 is treated as nearly constant core loss. Rated-current copper loss PkN falls to β²·PkN at load fraction β. Useful output is β·SN·power factor.
η = β·SN·cosφ / [β·SN·cosφ + P0 + β²·PkN]
P2 = β·SN·cosφPcu = β²·PkNη = P2/(P2+P0+Pcu)| Symbol / input | Meaning |
|---|---|
| Efficiency η (0 to 1) | Ratio of output real power to useful power plus modelled losses. |
| Rated apparent power SN in kVA | Nameplate apparent-power rating; enter its numerical kVA value through this power field. |
| Load fraction β | Current or apparent load divided by rated value; 0.75 means 75% load. |
| Power factor cos φ | Displacement factor of the connected load at the operating point. |
| No-load loss P0 | Real power measured at rated voltage in the no-load test, approximately core loss. |
| Rated copper loss PkN | Real power measured in the short-circuit test at rated current; scale by β squared at partial load. |
SN comes from the nameplate. β is actual current or apparent load divided by rated value. Power factor belongs to the load. P0 comes from the no-load test and PkN from the rated-current short-circuit test.
Ensure all data refer to the same transformer, tap and temperature condition. Obtain β and power factor at the actual operating point, then compare several load points rather than rated load only.
10 kVA at β=0.75 and power factor 0.8 delivers 6.0 kW. With 120 W core loss and 0.75²·300 W=168.75 W copper loss, η=6000/6288.75≈95.4%.
At low load P0 dominates; at high load copper loss grows quadratically. Maximum efficiency occurs approximately when the two loss components are equal.
Enter SN numerically in kVA; in the real-power balance 1 kVA contributes 1 kW per unit power factor. P0 and PkN may be entered in watts.
Loading comparisons, choosing several small versus one large transformer, and evaluating teaching experiments.
Constant voltage and equivalent losses. Temperature-dependent winding resistance, stray/harmonic loss and thermal transients are excluded.
Common mistake: Do not use apparent power directly as useful real power; power factor is essential. Scale PkN with β squared, not linearly.
Loading comparisons, choosing several small versus one large transformer, and evaluating teaching experiments.
SN comes from the nameplate. β is actual current or apparent load divided by rated value. Power factor belongs to the load. P0 comes from the no-load test and PkN from the rated-current short-circuit test.
Constant voltage and equivalent losses. Temperature-dependent winding resistance, stray/harmonic loss and thermal transients are excluded.