Definition der Kurzschlussleistung S''k = √3·Un·I''k nach IEC 60909-0 (DIN EN 60909-0/VDE 0102)

Three-phase network short-circuit power

Short-circuit power is a measure of network stiffness at a connection point and is used to select switching devices.

MINTSI
01

Inputs

Apparent power corresponding to the short-circuit current at the considered network point; shown here in the same unit as a real power, conventionally labelled kVA/MVA.

Rated line-to-line voltage at the considered network point.

Expected or measured three-phase short-circuit current at the network point.

02

Result

Select a target and calculate.

Calculation

S''k = √3 · U · Ik

Short-circuit power is a measure of network stiffness at a connection point and is used to select switching devices.

Understand the inputs
  • Short-circuit power S''kApparent power corresponding to the short-circuit current at the considered network point; shown here in the same unit as a real power, conventionally labelled kVA/MVA.
  • Network rated voltage URated line-to-line voltage at the considered network point.
  • Short-circuit current IkExpected or measured three-phase short-circuit current at the network point.
Example

U=400 V and Ik=5,000 A give S''k=√3·400·5,000≈3,464 kVA (3.46 MVA).

Assumptions and limits

Balanced three-phase fault with steady short-circuit current; initial symmetrical short-circuit current, peak short-circuit current and network impedance behaviour are not distinguished separately.

Technical article

Understand Three-phase network short-circuit power

This calculator determines short-circuit power at a network connection point from rated voltage and the short-circuit current occurring there, a key figure for grid-connection assessment.

What does this quantity describe?

Short-circuit power combines voltage and short-circuit current into an apparent power: S''k=√3·U·Ik. It describes how "stiff" the network is at that point.

Formula and variables

S''k = √3 · U · Ik

  • S''k = √3 · U · Ik
Symbol / inputMeaning
Short-circuit power S''kApparent power corresponding to the short-circuit current at the considered network point; shown here in the same unit as a real power, conventionally labelled kVA/MVA.
Network rated voltage URated line-to-line voltage at the considered network point.
Short-circuit current IkExpected or measured three-phase short-circuit current at the network point.

Choose the inputs correctly

U is the rated line-to-line voltage at the network point, Ik the expected or measured three-phase short-circuit current there.

How to use the calculator

Take U from the grid connection, Ik from a short-circuit calculation, a network operator's datasheet or a measurement.

Worked example

U=400 V and Ik=5,000 A give S''k=√3·400·5,000≈3,464 kVA (3.46 MVA).

Understand the result and units

High short-circuit power means a stiff network with low internal impedance; it determines the required breaking capacity of fuses and circuit breakers.

U is a voltage, Ik a current. S''k is shown in the same power unit as a real power, conventionally labelled kVA or MVA.

Useful next calculation

For the short-circuit current of a single transformer, see transformer short-circuit current.

Typical applications

Selecting switching devices and fuses by rated short-circuit breaking capacity, and assessing grid connection quality for high-power loads.

Assumptions, limits and common mistakes

Balanced three-phase fault with the steady-state short-circuit current; initial symmetrical short-circuit current, peak short-circuit current and the exact network impedance per IEC 60909 are not distinguished separately.

Common mistake: Do not confuse the single-phase with the three-phase short-circuit current; this formula assumes a balanced three-phase fault.

Frequently asked questions

What is “Three-phase network short-circuit power” used for?

Selecting switching devices and fuses by rated short-circuit breaking capacity, and assessing grid connection quality for high-power loads.

Where do the input values come from?

U is the rated line-to-line voltage at the network point, Ik the expected or measured three-phase short-circuit current there.

What does the result not cover?

Balanced three-phase fault with the steady-state short-circuit current; initial symmetrical short-circuit current, peak short-circuit current and the exact network impedance per IEC 60909 are not distinguished separately.