λ = P / (U·I)
Power factor is the share of apparent power U·I converted into real power.
Power factor is the share of apparent power U·I converted into real power.
Select a target and calculate.
Power factor is the share of apparent power U·I converted into real power.
P=1,800 W, U=230 V and I=10 A give S=2,300 VA and λ≈0.783.
Single-phase steady operation with simultaneous measurements; displacement and distortion power factor are not separated.
This calculator determines what share of apparent electrical power is converted into real power. It is intended for simultaneous measurements on a single-phase AC load.
Apparent power is S=U·I and λ=P/S ideally lies between 0 and 1. Only with sinusoidal voltage and current and no distortion may λ be read directly as cos φ.
λ = P / (U·I)
S = U · Iλ = P/S = P/(U·I)| Symbol / input | Meaning |
|---|---|
| Power factor λ | Ratio of real to apparent power; equal to cos φ only for sinusoidal quantities without harmonics. |
| Real power P | Measured average real power consumed by the load, not apparent power in VA. |
| RMS voltage U | RMS voltage directly across the single-phase load under consideration. |
| RMS current I | RMS total load current in the same operating state as P and U. |
P comes from a real-power meter or reliable watt rating. U and I are RMS values measured directly at the same load, simultaneously and in the same operating state.
Measure real power, voltage and current after the load settles. Enter all three and interpret λ together with load type and possible harmonic content.
1,800 W at 230 V and 10 A corresponds to 2,300 VA apparent power and λ≈0.783.
λ≈0.783 means conductors, switches and source carry 2.3 kVA although only 1.8 kW is converted. It does not identify whether phase shift or distortion is responsible.
P in W/kW, U in V and I in A; λ is dimensionless and displayed as a decimal. 0.9 means 90%.
Plausibility checks for motors, transformers, power supplies and other single-phase loads, and preparation for reactive-power or harmonic analysis.
No three-phase evaluation and no separation of displacement factor cos φ from distortion factor. Measurement error, startup and changing loads are excluded.
Common mistake: Do not enter VA as W or combine nameplate values from different operating points. For switch-mode supplies do not automatically equate λ with cos φ.
Plausibility checks for motors, transformers, power supplies and other single-phase loads, and preparation for reactive-power or harmonic analysis.
P comes from a real-power meter or reliable watt rating. U and I are RMS values measured directly at the same load, simultaneously and in the same operating state.
No three-phase evaluation and no separation of displacement factor cos φ from distortion factor. Measurement error, startup and changing loads are excluded.