t = U · Q · η / P
Runtime = usable energy / load power; efficiency and reserve reduce theoretical time.
Runtime = usable energy / load power; efficiency and reserve reduce theoretical time.
Select a target and calculate.
Runtime = usable energy / load power; efficiency and reserve reduce theoretical time.
48 V · 50 Ah · 0.85 / 480 W = 4.25 h.
Constant load and average voltage; temperature, ageing and discharge curve are excluded.
This calculator finds the theoretical runtime t of a battery under a constant load from voltage U, capacity Q, efficiency η and load power P — or solves for any one of these given the other three. It explains why actual runtime is usually below the simple ratio of nominal energy to power.
Theoretical runtime follows from the battery's usable energy (U·Q·η) divided by the constant load power P: t = U·Q·η/P. Efficiency η bundles losses from the discharge curve, internal resistance and any downstream converter.
Much like a fuel tank, a battery runs out sooner under higher power draw: doubling load power P at the same capacity roughly halves runtime — provided efficiency stays constant throughout the discharge.
t = U · Q · η / P
t = U · Q · η / PP = U · Q · η / tQ = P · t / (U · η)| Symbol / input | Meaning |
|---|---|
| Runtime t | Theoretical supply duration at constant load. |
| Average battery voltage U | Average voltage during discharge. |
| Capacity Q | Rated capacity; usable fraction is represented by efficiency. |
| Load power P | Electrical input power including continuous auxiliaries. |
| Overall efficiency η | Share of nominal energy usable after converter and discharge losses. |
Enter the three known quantities to find the fourth. Efficiency η ranges between 0 and 1 (or 0-100%) and bundles all losses between nominal energy and the energy actually usable at the load.
Select the target quantity and enter the three known values with units. Without more precise manufacturer data, an efficiency of about 0.8-0.9 for battery plus converter is a reasonable first estimate.
Given U = 48 V, Q = 50 Ah, P = 480 W and η = 0.85, substitution gives t = 48 V · 50 Ah · 0.85 / 480 W ≈ 4.25 h.
A calculated runtime of 4.25 hours is an approximation under constant load. In practice, actual runtime can differ if load fluctuates, battery temperature is outside the rated range, or the manufacturer specifies a C-rate-dependent capacity reduction.
Runtime is given in hours (h), capacity in amp-hours (Ah), power in watts (W) and voltage in volts (V). Efficiency η is dimensionless.
Runtime estimates are used to size backup power supplies, mobile devices, e-bikes and small electric vehicles, and to dimension battery storage for a defined bridging time.
The formula assumes constant power, a discharge-averaged voltage, and constant efficiency. Real batteries deliver less usable capacity at high discharge currents (high C-rate) than the simple calculation implies — an effect manufacturer datasheets often show as a capacity-vs-C-rate curve.
Common mistake: Do not neglect efficiency: without η, runtime is systematically overestimated. Also, do not assume nominal capacity stays constant regardless of actual discharge current, since high currents can reduce a real cell's usable capacity.
For battery plus a downstream converter, 0.8-0.9 is a common first estimate; for precise sizing, use the actual datasheet.
High discharge currents, low temperatures and cell ageing reduce usable capacity below the nominal rating, an effect this simple formula does not capture.
All else equal, runtime roughly halves, since t is inversely proportional to P.